Ashburn: loss of power feed B, two servers offline

A utility event at the Ashburn facility took feed B for 19 minutes. Two servers had both power cords on feed B and went offline.

Timeline

All times UTC, January 22, 2026.

  • Monitoring. Feed B voltage alarm on three racks in ASH1. Facility notifies us of a utility transfer event.
  • Investigating. Two servers (customers notified directly) lose power. All other servers continue on feed A.
  • Identified. Per-outlet metering shows both power supplies of both servers drawing from feed B. The servers were re-cabled a week earlier after a power supply swap.
  • Mitigating. Facility reports generator transfer complete on feed B.
  • Resolved. Remote hands power the servers back on. Both are reachable by 03:31.

Postmortem

The utility event itself was handled as designed by the facility. Our failure was cabling. After a power supply replacement on January 15 the technician connected both cords to feed B. A new check compares per-outlet metering against the intended A/B assignment and runs after every hardware change. We audited all 18 racks and found no further cases. 19 minutes is within the monthly allowance and no credit was due, but we credited the affected customer.